Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03921
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/14/2008 | ELECTRIC - FINAL | Approved | PORTABLE APPLIANCE MAY BE UNPLUGGED AT RECEPTACLE. BUILDING ELECTRIC HAS BEEN APPROVED BY RICK HOLLANDER. OK FOR FINAL. | |
04/10/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. ESPRESSO MACHINE LISTING LABEL WAS INSTALLED IN FIELD -- CUSTOMER STATES UNIT IS REFURBISHED AND RELABELED IN FIELD |
|
04/07/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ALL EQUIPMENT TO BE LISTED & LABELED - 110.3 PLEASE VERIFY 2. BOX OVERFILLED 3. EXIT SIGN NOT LISTED AS A JUNCTION BOX 4. BOXES MORE THAN 1/8" AROUND - 314.21 5. PANEL DIRECTORY TO BE AS PER 408.4 NO ABBREVIATIONS 6. THERE IS NO LIGHTING IN STORAGE AREA - WHAT IS HAPPENING FOR ILLUMINATION 7. EXTERIOR LIGHTING NOT AS PER PLANS. PLEASE REVISE AND SHOW OUTDOOR LIGHTING CALC'S |