Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2008 | FIRE - FINAL | Approved | LIGHTS INSTALLED AND FUNCTIONAL | |
| 07/29/2008 | FIRE - FINAL | Partial Approval | NEED EM. LIGHTS ON THIRD FLOOR. | |
| 07/11/2008 | FIRE - FINAL | Partial Approval | Temp C of O approved Clear all exit stairs Paint removed dampers working properly. |
|
| 07/07/2008 | FIRE - FINAL | Denied | Due to paint on dampers when testing the operations of the dampers they failed to fall in place. Repair fire dampers in air returns to stairwells, replace all painted 165 deg fire links. |