Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/10/2008 | FIRE SPKLR - FINAL | Approved | ||
| 07/07/2008 | FIRE SPKLR - FINAL | Denied | Need approved plans and permits from sprinkler contractor for all added sprinkler heads. On 4th floor add sprinkler coverage in closet. Due to paint on dampers when testing the operations of the dampers they failed to fall in place. Repair fire dampers in air returns to stairwells, replace all painted 165 deg fire links. |