Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2008 | ELECTRIC - FINAL | Approved | ||
| 07/28/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PREVIOUS INSPECTION ITEMS FROM 3RD & 4TH COMPLETED 2. STILL NEED TO ADDRESS EM LIGHTING ISSUE FOR 3RD FLOOR 3. NEED TO ADDRESS ISSUE WITH FAN COIL UNITS IN ELECTRIC CLOSETS 3RD & 4TH FLOOR SEE INSPECTION FROM 7/8/08 |
|
| 07/25/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 4TH FLOOR 1. SECURE BOX I.T ROOM 2. STRAP HOME RUNS WITHIN 12" OF GUTTER 3. SOME EM LIGHTS NOT WORKING 4. WIRE NUT NEUTRALS IN DISCONNECTS |
|
| 07/24/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 3RD FLOOR 1. INSTALL DISCONNECTING MEANS FOR FAN COIL UNIT I.T CLOSET 2. BONDING JUMPER FROM XFMRS TO PANELS TO BE #2 NEC 250.30 3. SEAL OPEN KNOCKOUTS RACEWAYS ELECTRIC CLOSETS 4. ALL CONDUCTORS TO RUN IN SAME RACEWAY 5. STRAP HOMERUNS WITHIN 12" OF GUTTERS 6. GROUNDING ELECTRODE CONDUCTOR TO TERMINATE ON NEUTRAL (XO) IN XFMR 7. NEED TO VERIFY TO SEE IF EM LIGHTING IS NEEDED FOR 3RD FLOOR 8. STRAP 2 1/2" EMT TO PANEL CP3A |
|
| 07/23/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEED TO ACCESS ALL DEVICES NEED TO HAVE EQUIPMENT OPEN FOR INSPECTIONS WILL NEED TO LOOK UNDER FLOORS HAVE OPEN FOR INSPECTION THIS WILL BE EARLY AM INSPECTION |