Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/28/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/03/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. NO ABOVE CEILING. THIS IS FLOOR INSPECTION 2. NEED TO STRAP HOMERUN CABLES MIN. EVERY 6' AND WITHIN 12" OF TERMINATIONS. NEC 3. CHECK DERATING OF HOME RUN CABLES IN GUTTER ELECTRIC CLOSET. NEC 310.15 & 366 4. WILL NEED TO MOVE MINI SPLIT FROM ABOVE PANEL 4TH FLOOR ELECTRIC CLOSET NEC 110. ALSO 3RD FLOOR CLOSET. 5. OK TO ENERGIZE PANELS L3A & L4A |
|