Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES ON FINAL PROVIDE AIR BALANCE REPORT, LABEL CONDENSOR ON ROOF & PROVIDE A SERVICE RECEPTACLE WITHIN 25' OF EQUIPMENT, FINISH CONNECTING DUCT SMOKE DETECTOR |
|
| 10/11/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SUSPENDED ROUGH DUCT OK TO PROCEED |