Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM03900
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/30/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/19/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLAN CALLS FOR LIGHTING TO BE 277V 2. NEED TO REMOVE 2X4 TEMP LIGHTING ABOVE CEILING 3. REMOVE TEMP PANEL FROM ABOVE CEILING 4. SERVICE IS NOT PER PLAN 5. DUCT SMOKE DETECTOR NOT WIRED |
|
10/11/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK UNDERGROUND OK WALLS OK FRONT SOFFIT |