Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/28/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SHEETMETAL SCREWS NOT ALLOWED TO CONNECT GROUND LUGS IN GUTTER AND J-BOX --- NEC 250.8 2. REMOVE ALL PAINT FROM BEHIND LUGS SO THEY HAVE FULL FOOT CONTACT TO BARE METAL -- NEC 250.12 3. USE MINIMUM #6 CU PHONE BOARD GROUND - NEC 250.64B NEC 250.120C |
|
| 04/25/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. IDENTIFY SPACE AT SERVICE DISCONNECT 2. CLOSE ALL PANELS & BUCKET DOOR AT SERVICE 3. REMOVE ALL PAINT UNDER LUG IN FEEDER J-BOX 4. PLANS DO NOT SHOW ANY NEW WIRING TO PATIENT AREAS 5. INSTALL A PERMANENT PANEL DIRECTORY - DUCT TAPE NOT ACCEPTABLE, BREAKERS ARE TO BE NUMBERED 6. GROUND TO PHONE BOARD TO BE PER NEC 800.100 7. GROUND BRANCH CKT GUTTER |