Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07CM03898

Parcel: 13317062A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/29/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/28/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHEETMETAL SCREWS NOT ALLOWED TO CONNECT GROUND LUGS IN GUTTER AND J-BOX --- NEC 250.8
2. REMOVE ALL PAINT FROM BEHIND LUGS SO THEY HAVE FULL FOOT CONTACT TO BARE METAL -- NEC 250.12
3. USE MINIMUM #6 CU PHONE BOARD GROUND - NEC 250.64B
NEC 250.120C
04/25/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. IDENTIFY SPACE AT SERVICE DISCONNECT
2. CLOSE ALL PANELS & BUCKET DOOR AT SERVICE
3. REMOVE ALL PAINT UNDER LUG IN FEEDER J-BOX
4. PLANS DO NOT SHOW ANY NEW WIRING TO PATIENT AREAS
5. INSTALL A PERMANENT PANEL DIRECTORY - DUCT TAPE NOT ACCEPTABLE, BREAKERS ARE TO BE NUMBERED
6. GROUND TO PHONE BOARD TO BE PER NEC 800.100
7. GROUND BRANCH CKT GUTTER