Permit: T07CM03897

Parcel: 10408005D

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
02/21/2008 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
02/15/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
CORRECTIONS OK
OK TO COVER
RECALL FOR PRE-SLAB INSP
02/14/2008 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 3" WASTE LINE REQUIRES A 3" C.O
2. PROVIDE MIN. TRAP ARM DISTANCE, 4"
3. VENT TAKE OFFS SHALL BE ABOVE THE FLOW LINE. TO ACCOMPLISH THIS ROLL VENT FITTINGS UP AT A TRUE 45 DEG ANGLE. USE AN 1/8 BEND ON YOUR COMBO, USE A 1/16TH BEND WITH A WYE FITTING
4. OFFSET VENT AT MS
5. REMOVE ANY WET DIRT AROUND FITTINGS
OUTSIDE PIPING IS OK