Permit: T07CM03897

Parcel: 10408005D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/03/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/02/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLETE ALL PREVIOUS CORRECTIONS
LETTER CONCERNING DELETION OF ISOLATED GROUND CKT RECEIVED
04/01/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/31/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION

1. MISSING EXTERIOR EMERGENCY LIGHTS
2. EMERGENCY LIGHTING TO BE POWERED BY NORMAL LIGHTING CKT FOR THAT AREA -- SEE NEC 700.12F
3. PANEL DIRECTORY NOT CORRECT -- NEC 408.4
4. WATER HEATER DISCONNECTING MEANS TO HAVE PROPER FRONT WORKING CLEARANCE (NEC 110.26) OR (NEC 422.31B IN FUTURE)
5. PROVIDE GFI PROTECTION PER PLAN
6. PLANS CALL FOR ISOLATED GROUND TYPE CKT FOR R.O'S RECEPTACLES
7. CONDENSORS - DISCONNECTS TO HAVE PROPER FRONT CLEARANCE, FREEZER TO BE MAX 15 AMP FUSE PER DATA PLATE
8. BOXES TO BE PROPERLY GROUNDED AND SEALED
NEED INHIBITOR FOR ALUMINUM TERMINATIONS HAVE OVERFILLED WIRE NUTS
9. EZ-MC TO BE USED AL IT IS LISTED