Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/03/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/02/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* COMPLETE ALL PREVIOUS CORRECTIONS LETTER CONCERNING DELETION OF ISOLATED GROUND CKT RECEIVED |
|
| 04/01/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/31/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION 1. MISSING EXTERIOR EMERGENCY LIGHTS 2. EMERGENCY LIGHTING TO BE POWERED BY NORMAL LIGHTING CKT FOR THAT AREA -- SEE NEC 700.12F 3. PANEL DIRECTORY NOT CORRECT -- NEC 408.4 4. WATER HEATER DISCONNECTING MEANS TO HAVE PROPER FRONT WORKING CLEARANCE (NEC 110.26) OR (NEC 422.31B IN FUTURE) 5. PROVIDE GFI PROTECTION PER PLAN 6. PLANS CALL FOR ISOLATED GROUND TYPE CKT FOR R.O'S RECEPTACLES 7. CONDENSORS - DISCONNECTS TO HAVE PROPER FRONT CLEARANCE, FREEZER TO BE MAX 15 AMP FUSE PER DATA PLATE 8. BOXES TO BE PROPERLY GROUNDED AND SEALED NEED INHIBITOR FOR ALUMINUM TERMINATIONS HAVE OVERFILLED WIRE NUTS 9. EZ-MC TO BE USED AL IT IS LISTED |