Permit: T07CM03870

Parcel: 13329010A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/13/2008 ELECTRIC - FINAL Approved
03/12/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SIGN CIRCUIT TO BE SEPARATE FROM LIGHTING 600.5
2. BOXES 314.20

NO BUILDING ON PERMIT - OK TEMP C OF O
03/11/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BRANCH CIRCUITS TO BE IDENTIFIED HIGH LEGS
2. CLEAN EXCESS DIRT FROM PANELS
3. PLEASE VERIFY LISTING ON ECOLABS, DISHWASHER,
ROSS UNIT
4. ALL KITCHEN CONVENIENCE RECEPTACLES TO BE GFCI PROTECTED - 210.8(B)
5. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
6. LABEL PANEL "A" AS PER 408.4
7. EXIT & EM LIGHTS TO BE AS PER 700.12 -
ALSO NOT WORKING
8. PENDANT LIGHTS TO BE WRENCHTIDE
9. CLEAN SURFACE UNDER LUG JUNCTION BOX ROOF - 250.12
10. 240V DELTA LABEL TO BE EVIDENT
11. WHERE ARE RECEPTACLES FOR TV'S UP HIGH -
NOT ON PLANS