Permit: T07CM03869

Parcel: 13101432D


Addresses:

1252 S CRAYCROFT RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM03869

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/22/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) OK FOR FINAL
03/26/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PERMANENTLY I.D. A/C UNITS
2) MARK UNIT DATA PLATE AND FUSE ACCORDINGLY
3) PROVIDE A PERMIT FOR NEW TRAMA UNIT
4) DO NOT USE WHITE WIRES TO POWER A/C UNITS
5) REVISE PLANS TO SHOW ACTUAL MECH SYSTEMS INSTALLED
6) SUPPORT PVC ON ROOF EVERY 4'
7) CAP OFF UNUSED GAS LINES
8) PROVIDE AIR BALANCE REPORT