Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) PLEASE HAVE PLANS ON SITE FOR ALL FUTURE INSPECTIONS 2) RECALL AFTER SWING OVER COMPLETE |
|
| 01/23/2008 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL GROUNDING ELECTRODES TO BE BONDED TOGETHER @ BUILDING SEE PLAN SHEET E-3 2. BONDING JUMPER TO NIPPLE NOT SIZED PROPERLY TO BE #4 NEC 250.92, NEC 250.102, 250.66 ONLY BOND ONE END OF NIPPLE. DO NOT NEED TO BOND BOTH ENDS & DO NOT RUN BONDING JUMPER FROM NEUTRAL BAR -- IS METER TO NEUTRAL BAR IN PANEL 3. MARK "SERVICE DISCONNECT" |