Permit: T07CM03858

Parcel: 11203347E

Inspection Status: Partial Approval

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
01/25/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) PLEASE HAVE PLANS ON SITE FOR ALL FUTURE INSPECTIONS
2) RECALL AFTER SWING OVER COMPLETE
01/23/2008 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL GROUNDING ELECTRODES TO BE BONDED TOGETHER @ BUILDING SEE PLAN SHEET E-3
2. BONDING JUMPER TO NIPPLE NOT SIZED PROPERLY
TO BE #4 NEC 250.92, NEC 250.102, 250.66
ONLY BOND ONE END OF NIPPLE. DO NOT NEED TO BOND BOTH ENDS & DO NOT RUN BONDING JUMPER FROM NEUTRAL BAR -- IS METER TO NEUTRAL BAR IN PANEL
3. MARK "SERVICE DISCONNECT"