Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/30/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 07/29/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 07/22/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 113 REMOVE PAINT FROM UNIT DATA PLATE, SEAL MED. PRESSURE DUCT AND INSULATE 2) 111-ELECTRIC ROOM COMPLETE MINI SPLIT 3) PROVIDE LETTER FROM ENGINEER ON S.D. IN SUPPLY 4) PROVIDE ALUM DUCT IN SHOWER EXHAUST PER SPEC 15890 2.02 B 5) IDENTIFY DUCT WIHT LAMB PLATES 15190 3.02 C.M.U 3) MECHANICAL FASTEN INSULATION PER SPEC 15290.2 3.02 |
|
| 04/27/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 04/24/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SUPPLY & EXHAUST IN RESTROOMS IN NORTH ADDITION OK TO SHEETROCK MECHANICAL ONLY OK TO SHEETROCK HARD LID IN NORTH ADDITION OPEN AREA |
|
| 02/06/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* EXISTING GYM LOBBY WRAP AROUND AND DOWN TO EXISTING PIPING HW/CW PRESSURE TEST OK |
|
| 12/23/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) HW/LW PIPING FROM EXISTING HOT TAP TO EXISTING EXTERIOR WALL (3 HR) PENETRATION HYDRO TEST OK 100 + PSI |