Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2009 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/22/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/10/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CHECKED 100 PSI TEST HYDRONIC PIPING HOT AND COLD EAST MECH. MEZZANINE. OK TO COMPLETE INSULATION |
|
| 06/11/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CHILLER AND HOT WATER PIPING FROM ROOF PENETRATION TO AIR HANDLER NOT HOLDING PRESSURE |
|
| 05/12/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 100 PSI TEST ON CHILLED AND HOT PIPING ABOVE GYM AND CORRIDOR AND OFFICE VAV's -- OK TO INSULATE |
|
| 04/24/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 02/06/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |