Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
| 09/03/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED DISCONNECTING MEANS ROLL UP MOTORS 2) RECEPTACLE COVERS TO BE FOR WET LOCATION WEATHER OR NOT PLUGGED INTO 406.8 3) AHV-3: BOND BUSHING AND 250.8 4) LABEL BALLAST CONTROL BOXES 5) BOND OVER 250 VOLTS AT CONCENTRICS 250.97 |
|
| 08/24/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK MAIN GYM LOBBY AND ROOMS 001-003 2) OK ROOMS 101-105, 129 3) OK PANEL "PGPE" 4) OK BASKET BALL MOTORS "CSA" 5) RECEIVED LETTER FOR ATS WORKING CONDITIONS |
|
| 08/21/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
| 08/10/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE VERIFY LISTING FOR BASKET BALL BACK BOARD RAISE ASSEMBLY 2) BOXES NO MORE THAN 1/8" AROUND 314.21 |
|
| 08/04/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* TUNNEL: 1) LABEL EQUIPMENT 210.5 (C) ALSO PANEL DIRECTORY 408.4 2) FILL UNUSED OPENINGS IN PANEL 3) BOND BUSHING-EM LIGHTING DISCONNECT 250.97 4) ONLY ONE CONDUCTOR PER LUG-DISCONNECTS 5) BUILDING INSPECTOR TO VERIFY IF FIRE STOPPING IS NEEDED MECHANICAL MEZZINE: 1) LABEL EQUIPMENT PER 210.5 (C) 2) SUPPORT CONDUITS AND TIGHTEN FITTINGS (CANNOT STRAP TO DUCT WORK) 3) BOND BUSHINGS AT REMOVE BALLAST 250.97 |
|
| 07/29/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 07/24/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NO MORE THAN 360 DEGREE IN CONDUIT RUNS-MECHANICAL ROOM ?-4 2) PLEASE PROVIDE A COPY OF ATS SYSTEM WORKING CONDITIONS 3) OK ROOMS #118-128 FOR FINAL ELECRIC |
|
| 07/16/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FILL UNUSED OPENINGS-HAND DRYER 2) SECURELY ATTACH FIXTURES TO GRID 410.16-IF MANUFACTURERS CLIP ARE USED, MUST BE EFFECTIVE 3) PLEASE VERIFY LISTING FOR ORANGE ENT PER 362.6 4) FINISH SUPPORTING VDV CABELING 5) OK LIGHTS ROOMS #114,117,112,108,121-128, 118 & 119 INGRIDS |