Permit: T07CM03855

Parcel: 118050010

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/08/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK ELECTRIC
09/03/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NEED DISCONNECTING MEANS ROLL UP MOTORS
2) RECEPTACLE COVERS TO BE FOR WET LOCATION WEATHER OR NOT PLUGGED INTO 406.8
3) AHV-3: BOND BUSHING AND 250.8
4) LABEL BALLAST CONTROL BOXES
5) BOND OVER 250 VOLTS AT CONCENTRICS 250.97
08/24/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK MAIN GYM LOBBY AND ROOMS 001-003
2) OK ROOMS 101-105, 129
3) OK PANEL "PGPE"
4) OK BASKET BALL MOTORS "CSA"
5) RECEIVED LETTER FOR ATS WORKING CONDITIONS
08/21/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
08/10/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PLEASE VERIFY LISTING FOR BASKET BALL BACK BOARD RAISE ASSEMBLY
2) BOXES NO MORE THAN 1/8" AROUND 314.21
08/04/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
TUNNEL:
1) LABEL EQUIPMENT 210.5 (C) ALSO PANEL DIRECTORY 408.4
2) FILL UNUSED OPENINGS IN PANEL
3) BOND BUSHING-EM LIGHTING DISCONNECT 250.97
4) ONLY ONE CONDUCTOR PER LUG-DISCONNECTS
5) BUILDING INSPECTOR TO VERIFY IF FIRE STOPPING IS NEEDED
MECHANICAL MEZZINE:
1) LABEL EQUIPMENT PER 210.5 (C)
2) SUPPORT CONDUITS AND TIGHTEN FITTINGS (CANNOT STRAP TO DUCT WORK)
3) BOND BUSHINGS AT REMOVE BALLAST 250.97
07/29/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
07/24/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NO MORE THAN 360 DEGREE IN CONDUIT RUNS-MECHANICAL ROOM ?-4
2) PLEASE PROVIDE A COPY OF ATS SYSTEM WORKING CONDITIONS
3) OK ROOMS #118-128 FOR FINAL ELECRIC
07/16/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FILL UNUSED OPENINGS-HAND DRYER
2) SECURELY ATTACH FIXTURES TO GRID 410.16-IF MANUFACTURERS CLIP ARE USED, MUST BE EFFECTIVE
3) PLEASE VERIFY LISTING FOR ORANGE ENT PER 362.6
4) FINISH SUPPORTING VDV CABELING
5) OK LIGHTS ROOMS #114,117,112,108,121-128, 118 & 119 INGRIDS