Permit: T07CM03855

Parcel: 118050010

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/08/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/29/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/06/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) LABEL PANEL COVERS PER 210.5 (C)
2) NEED ILLUMINATION AT EQUIPMENT 110.26 (D)
3) MAINTAIN WORKING CLEARANCES 110.26 (A)
4) NEED GROUNDING ELECTRODE SYSTEM FOR TRANSFORMER
5) LABEL MOTOR STARTS
6) DISCONNECT NOT IN COMPLIANCE WITH TAP RULES 240
7) OK FLOOR BOXES GYM FLOOR
8) OK TO ENERGIZE SUBJECT TO BOND
9) CONTRACTOR TO MAINTAIN LOCKOUT/TAG OUT
06/25/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
DO NOT COVER WITHOUT INSPECTION CLEARANCES

OK EXTERIOR WEST OUTSIDE HIGH
OK CONNECTIONS IN EXISTING G.E. GEAR
06/23/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
*MAINTAIN CLEARANCES PER 110.26

A BOND WILL BE NEEDED FOR TEMP POWER
06/19/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
06/15/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK EXTERIOR EAST AND NORTHEAST OUTSIDE HIGH

1. VDV CABLING TO BE AS PER 725.24, 800.24, 300.11
06/08/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED
06/05/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PLEASE VERIFY BOX FILL FIRE ALARM BOX
2. SUPPORT VDV CABLING PER 725.3 & 24, 800.3 & 24, 300.11
3. OK HARD LIDS 102-104, EXTERIOR SOFFITS EAST & NORTH OUTSIDE
05/28/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/21/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK MEZZINE MECHANICAL ROOM WALL
2) EMS TO COME OUT OF WALL
04/15/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS ROOMS 108, 121-128 AND 003
02/27/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK REMAINDER OF RETAINING WALL LIGHTS
02/18/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK WALL LTG. AT SOUTHEAST RETAINING WALL
2. OK U.G CONCESSION LOBBY
02/09/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK RECESSED LTG. (4) AT STADIUM AREA S.W. RETAINING
01/13/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/12/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
NEW LOBBY RECEPTACLE OK
5 - 3/4 & 2 - 1" & 2 - 1' PVC
1 - 4'
5 - 3"
2 - 2" SLEEVES WEST WALL OF CONCESSION AREA
12/23/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CONCESSION WALLS ROUGH