Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/29/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/06/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) LABEL PANEL COVERS PER 210.5 (C) 2) NEED ILLUMINATION AT EQUIPMENT 110.26 (D) 3) MAINTAIN WORKING CLEARANCES 110.26 (A) 4) NEED GROUNDING ELECTRODE SYSTEM FOR TRANSFORMER 5) LABEL MOTOR STARTS 6) DISCONNECT NOT IN COMPLIANCE WITH TAP RULES 240 7) OK FLOOR BOXES GYM FLOOR 8) OK TO ENERGIZE SUBJECT TO BOND 9) CONTRACTOR TO MAINTAIN LOCKOUT/TAG OUT |
|
| 06/25/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DO NOT COVER WITHOUT INSPECTION CLEARANCES OK EXTERIOR WEST OUTSIDE HIGH OK CONNECTIONS IN EXISTING G.E. GEAR |
|
| 06/23/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* *MAINTAIN CLEARANCES PER 110.26 A BOND WILL BE NEEDED FOR TEMP POWER |
|
| 06/19/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
| 06/15/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK EXTERIOR EAST AND NORTHEAST OUTSIDE HIGH 1. VDV CABLING TO BE AS PER 725.24, 800.24, 300.11 |
|
| 06/08/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 06/05/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PLEASE VERIFY BOX FILL FIRE ALARM BOX 2. SUPPORT VDV CABLING PER 725.3 & 24, 800.3 & 24, 300.11 3. OK HARD LIDS 102-104, EXTERIOR SOFFITS EAST & NORTH OUTSIDE |
|
| 05/28/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 05/21/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK MEZZINE MECHANICAL ROOM WALL 2) EMS TO COME OUT OF WALL |
|
| 04/15/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS ROOMS 108, 121-128 AND 003 |
|
| 02/27/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK REMAINDER OF RETAINING WALL LIGHTS |
|
| 02/18/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WALL LTG. AT SOUTHEAST RETAINING WALL 2. OK U.G CONCESSION LOBBY |
|
| 02/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK RECESSED LTG. (4) AT STADIUM AREA S.W. RETAINING |
|
| 01/13/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 01/12/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NEW LOBBY RECEPTACLE OK 5 - 3/4 & 2 - 1" & 2 - 1' PVC 1 - 4' 5 - 3" 2 - 2" SLEEVES WEST WALL OF CONCESSION AREA |
|
| 12/23/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CONCESSION WALLS ROUGH |