Permit: T07CM03855

Parcel: 118050010

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
10/09/2009 BUILDING - FINAL Approved IVRS - Inspection :*
1) OK TCO
2) NO BOND
3) NO REINSPECTION FEE
10/02/2009 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) INSTALL MISSING ? TOILET GRAB BARS AND FLUSH LEVERS, NEED TO BE ON OPEN SIDE AND MISSING DRAIN INSULATION
2) DOOR SWEEP ON FIRE RATED DOORS
3) HC TOILETS 16" TO 18" TO CENTER OFF WALL
4) FIRE, MECHANICAL AND ELECTRIC APPROVE, NEED PLUMBING
5) NEED COMPLIANT SPECIAL INSPECTION CERT
6) NO HC PARKING OR ACC ROUTE TO BLDGS FROM EVENT PARKING
7) ICC/ANSI OR ADAAG?