Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2009 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection :* | |
| 05/11/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1ST LIFT PLUMBING CHASE OFF GATER ROOM |
|
| 04/30/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* GYM NORTHEAST 12" CMU WALL FROM 26' TO 32'8" AFFE OK TO GROUT -- SPECIAL INSPECTION BY RYAN OF TERRACON |
|
| 04/29/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. NORTH INFILL 21'4" TO 26' NO LAPS WITHIN 5' OF CONTROL JOINT 2. REQ. SPECIAL INSPECTION |
|
| 04/28/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. SOUTH WING WALLS TO 12' TOP OUT 2. NORTH INFILL TO 21' DUE TO CONDITIONS LIFT EXCEEDS 6' PENDING CLEANOUTS |
|
| 04/27/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* NORTH WALL @ 14' OK TO GROUT (12" CMU) |
|
| 04/24/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | 2ND LIFT INFILL AND SOUTH ENTRANCE | |
| 04/23/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) 1ST LIFT IN FILL NORTH SIDE & 1 WING WALL AND 2 WING WALLS SOUTH SIDE 2) NEEDS SPECIAL INSPECTION |
|
| 03/09/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* TOP OUT INTERIOR EAST MEZZ. WALLS TOP OUT |
|
| 02/26/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* NEED STAMPED RFI FOR MEZZANINE EXT WALL TOP CONTINUOUS BOND BEAM |
|
| 02/25/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* WEST WALLS OF RM. 102-105 4' TO 8' WEST WALL ROOM 101 4' TO 8' |
|
| 02/24/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. WEST WALL OF ROOMS 102, 103, 104, 105 TO 4' AFF 2. WEST WALL OF ROOM 101 3. TERRACON SPECIAL INSPECTED |
|
| 02/19/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. INTERIOR WALLS TO 9'4" TOP OUT 2. PENDING RFI REGARDING #4 JAMB BARS |
|
| 02/18/2009 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* | |
| 02/17/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. INTERIOR WALLS UNDER WEST MEZZANINE TO 4' NEED RFI FOR #4 BARS AT INTERSECTIONS AND CORNERS AND DOOR JAMBS 11 S-201 2. TERRACON SPECIAL INSPECTED |
|
| 02/13/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* TOP OUT MEZZANINE WALL |
|
| 02/12/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) 2ND LIFT MEZZINIME WALL AND CONCESSION WALLS |
|
| 02/11/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1ST LIFT INTERIOR MEZZANINE WALL; NORTH & SOUTH STAIR WING; SOUTH CONCESSION WALL |
|
| 02/10/2009 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* | |
| 02/09/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. TOP OUT ABOVE N STEEL LINTEL 2. CORRIDOR WALL OUTSIDE GATOR ROOM TOP OUT |
|
| 02/06/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* E, S, NE TOPOUT OK ABOVE N. STEEL LINTEL 24' TO 28' |
|
| 02/05/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. ABOVE S. STEEL LINTEL AND SE CORNER 24' TO 28' 2. ABOVE N. STEEL LINTEL 20' TO 24' 3. GATOR ROOM TOP OUT |
|
| 02/04/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. E.WALL PRACTICE GYM 24 TO 28 2. OVER SOUTH STEEL LINTEL 20 TO 24 3. CORRIDOR WALL OUTSIDE GATER ROOM 16' TO 20' 4. SPECIAL INSPECTED |
|
| 02/03/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. EAST WALL AND CORNERS 20' TO 24' 2. MASONRY ABOVE STEEL LINTEL NORTH SIDE 12 TO 16 3. TO BE SPECIAL INSPECTED |
|
| 02/02/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. E, SE CORNER, NE CORNER 16' TO 20' 2. SO. WALL ABOVE STEEL 12' TO 16' 3. TERRACON SPECIAL INSPECTED 4. GET JOIST SUBMITTALS APPROVED |
|
| 01/30/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. SE CORNER FROM S CONTROL JOINT TO STEEL LINTEL 12' TO 16' 2. ABOVE STEEL LINTEL 11 TO 15'8" 3. NE CORNER FROM STEEL LINTEL TO ACCESS OPENING 12' TO 16' 4. REVIEWED WELD SPECIAL INSPECTION OK |
|
| 01/29/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. N.WALL OF NE CORNER, S.WALL OF SE CORNER ON PRACTICE GYM 2. STORAGE RM. FROM 2 TO 6 3. TERRACON SPECIAL INSPECTED |
|
| 01/28/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. STEM WALL 8" INTERIOR MEZZ. STEM WALL (3-5-201) 2. SE & NE CORNERS OF GYM TO 8' 3. GATOR ROOM TO 8' 4. TO BE SPECIAL INSPECTED |
|
| 01/26/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 28-31'4" SOUTH, NORTH AND NORTHWEST WALLS |
|
| 01/23/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 24'-28' NORTH, NORTH WEST WALL |
|
| 01/22/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* SOUTHWEST WALL 24'-28'; WEST WALL 20'-24'; NORTHWEST WALL 20'-24' DIVIDER WALL ROOM #003 TOPOUT ; ROOM #002 4'-8' |
|
| 01/21/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. SW WALL 20' TO 24' AFF PRACTICE GYM 2. WEST AND NW WALL 16' TO 20' AFF 3. SPECIAL INSPECTED TERRACON |
|
| 01/20/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. SW CORNER OF PRACTICE GYM 16' TO 20' 2. GATOR STORAGE TO 4' 3. LOBBY INTERIOR DIVIDING WALL 12' TO 16'8" 4. WING WALL OF JANITOR CLOSET TO 4' 5. LOBBY EXTERIOR TOP OUT 6. NE 12" BLOCK TO 4' |
|
| 01/16/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* W, NW, SW, 12 T0 16 WITH SPECIAL INSPECTION |
|
| 01/15/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* MAIN GYM LOBBY TO 12' WITH SPECIAL INSPECTION |
|
| 01/14/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. WEST, N.WEST AND SOUTHWEST GYM WALLS TO 12' 2. TO BE SPECIAL INSPECTED 3. (3) ON S401 WITH CITY REVISIONS |
|
| 01/13/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. WEST 1/2 OF GYM 12" MASONRY TO 8' 2. SE CORNER OF NEW GYM TO 4' 3. EXTENDED LOBBY TO 8' 4. TERRACON SPECIAL INSPECTED |
|
| 01/12/2009 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* | |
| 01/09/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. EXTENDED LOBBY TO 4' 2. B SOUTH TO 8" WALL TO 4' 3. 32" MIN. MASONRY BAR LAP |
|
| 01/08/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* W, SW, NW - 12" EXTERIOR 12" GYM WALLS |
|
| 05/13/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* OK TO TOP OUT SANDWICH WALLS N&W GROUT CELLS WHERE PAPER HAS BEEN LEFT OFF TO ENCASE BOND BEAM SPECIAL INSPECTED |
|
| 05/12/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 12' TO 16' N&W SANDWICH WALL -- OK TO GROUT |
|
| 05/09/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* OK TO GROUT 3RD LIFT SANDWICH WALLS SPECIAL INSPECTED |
|
| 05/08/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* RFI 5/2/08 FROM EPOXY REBAR - SPECIAL INSPECTED OK TO GROUT 2ND LIFT SANDWICH WALLS SPECIAL INSPECTED |
|
| 05/07/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* OK TO GROUT 1ST LIFT SANDWICH WALL |