Permit: T07CM03855

Parcel: 118050010

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
05/12/2009 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
05/11/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1ST LIFT PLUMBING CHASE OFF GATER ROOM
04/30/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
GYM NORTHEAST 12" CMU WALL FROM 26' TO 32'8" AFFE
OK TO GROUT -- SPECIAL INSPECTION BY RYAN OF TERRACON
04/29/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. NORTH INFILL 21'4" TO 26' NO LAPS WITHIN 5' OF
CONTROL JOINT
2. REQ. SPECIAL INSPECTION
04/28/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. SOUTH WING WALLS TO 12' TOP OUT
2. NORTH INFILL TO 21' DUE TO CONDITIONS LIFT
EXCEEDS 6' PENDING CLEANOUTS
04/27/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
NORTH WALL @ 14'
OK TO GROUT (12" CMU)
04/24/2009 REINFORCED MASONRY PRE-GROUT Partial Approval 2ND LIFT INFILL AND SOUTH ENTRANCE
04/23/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 1ST LIFT IN FILL NORTH SIDE & 1 WING WALL AND 2 WING WALLS SOUTH SIDE
2) NEEDS SPECIAL INSPECTION
03/09/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
TOP OUT INTERIOR EAST MEZZ. WALLS TOP OUT
02/26/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
NEED STAMPED RFI FOR MEZZANINE EXT WALL TOP CONTINUOUS BOND BEAM
02/25/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
WEST WALLS OF RM. 102-105 4' TO 8'
WEST WALL ROOM 101 4' TO 8'
02/24/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. WEST WALL OF ROOMS 102, 103, 104, 105 TO 4' AFF
2. WEST WALL OF ROOM 101
3. TERRACON SPECIAL INSPECTED
02/19/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. INTERIOR WALLS TO 9'4" TOP OUT
2. PENDING RFI REGARDING #4 JAMB BARS
02/18/2009 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
02/17/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. INTERIOR WALLS UNDER WEST MEZZANINE TO 4' NEED RFI FOR #4 BARS AT INTERSECTIONS AND CORNERS AND DOOR JAMBS 11 S-201
2. TERRACON SPECIAL INSPECTED
02/13/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
TOP OUT MEZZANINE WALL
02/12/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 2ND LIFT MEZZINIME WALL AND CONCESSION WALLS
02/11/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1ST LIFT INTERIOR MEZZANINE WALL; NORTH & SOUTH STAIR WING; SOUTH CONCESSION WALL
02/10/2009 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
02/09/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. TOP OUT ABOVE N STEEL LINTEL
2. CORRIDOR WALL OUTSIDE GATOR ROOM TOP OUT
02/06/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
E, S, NE TOPOUT OK
ABOVE N. STEEL LINTEL 24' TO 28'
02/05/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. ABOVE S. STEEL LINTEL AND SE CORNER 24' TO 28'
2. ABOVE N. STEEL LINTEL 20' TO 24'
3. GATOR ROOM TOP OUT
02/04/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. E.WALL PRACTICE GYM 24 TO 28
2. OVER SOUTH STEEL LINTEL 20 TO 24
3. CORRIDOR WALL OUTSIDE GATER ROOM 16' TO 20'
4. SPECIAL INSPECTED
02/03/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. EAST WALL AND CORNERS 20' TO 24'
2. MASONRY ABOVE STEEL LINTEL NORTH SIDE 12 TO 16
3. TO BE SPECIAL INSPECTED
02/02/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. E, SE CORNER, NE CORNER 16' TO 20'
2. SO. WALL ABOVE STEEL 12' TO 16'
3. TERRACON SPECIAL INSPECTED
4. GET JOIST SUBMITTALS APPROVED
01/30/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. SE CORNER FROM S CONTROL JOINT TO STEEL
LINTEL 12' TO 16'
2. ABOVE STEEL LINTEL 11 TO 15'8"
3. NE CORNER FROM STEEL LINTEL TO ACCESS
OPENING 12' TO 16'
4. REVIEWED WELD SPECIAL INSPECTION OK
01/29/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. N.WALL OF NE CORNER, S.WALL OF SE CORNER ON PRACTICE GYM
2. STORAGE RM. FROM 2 TO 6
3. TERRACON SPECIAL INSPECTED
01/28/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. STEM WALL 8" INTERIOR MEZZ. STEM WALL (3-5-201)
2. SE & NE CORNERS OF GYM TO 8'
3. GATOR ROOM TO 8'
4. TO BE SPECIAL INSPECTED
01/26/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
28-31'4" SOUTH, NORTH AND NORTHWEST WALLS
01/23/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
24'-28' NORTH, NORTH WEST WALL
01/22/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
SOUTHWEST WALL 24'-28'; WEST WALL 20'-24';
NORTHWEST WALL 20'-24'
DIVIDER WALL ROOM #003 TOPOUT ; ROOM #002 4'-8'
01/21/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. SW WALL 20' TO 24' AFF PRACTICE GYM
2. WEST AND NW WALL 16' TO 20' AFF
3. SPECIAL INSPECTED TERRACON
01/20/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. SW CORNER OF PRACTICE GYM 16' TO 20'
2. GATOR STORAGE TO 4'
3. LOBBY INTERIOR DIVIDING WALL 12' TO 16'8"
4. WING WALL OF JANITOR CLOSET TO 4'
5. LOBBY EXTERIOR TOP OUT
6. NE 12" BLOCK TO 4'
01/16/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
W, NW, SW, 12 T0 16 WITH SPECIAL INSPECTION
01/15/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
MAIN GYM LOBBY TO 12' WITH SPECIAL INSPECTION
01/14/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. WEST, N.WEST AND SOUTHWEST GYM WALLS TO 12'
2. TO BE SPECIAL INSPECTED
3. (3) ON S401 WITH CITY REVISIONS
01/13/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. WEST 1/2 OF GYM 12" MASONRY TO 8'
2. SE CORNER OF NEW GYM TO 4'
3. EXTENDED LOBBY TO 8'
4. TERRACON SPECIAL INSPECTED
01/12/2009 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
01/09/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. EXTENDED LOBBY TO 4'
2. B SOUTH TO 8" WALL TO 4'
3. 32" MIN. MASONRY BAR LAP
01/08/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
W, SW, NW - 12" EXTERIOR 12" GYM WALLS
05/13/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
OK TO TOP OUT SANDWICH WALLS N&W GROUT CELLS WHERE PAPER HAS BEEN LEFT OFF TO ENCASE BOND BEAM
SPECIAL INSPECTED
05/12/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
12' TO 16' N&W SANDWICH WALL -- OK TO GROUT
05/09/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
OK TO GROUT 3RD LIFT SANDWICH WALLS SPECIAL INSPECTED
05/08/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
RFI 5/2/08 FROM EPOXY REBAR - SPECIAL INSPECTED
OK TO GROUT 2ND LIFT SANDWICH WALLS SPECIAL INSPECTED
05/07/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
OK TO GROUT 1ST LIFT SANDWICH WALL