Permit: T07CM03847

Parcel: 10602265B


Addresses:

320 W PRINCE RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/06/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
1. MC TO BE SECURED WITHIN 12" OF ENCLOSURES/TERMINATIONS
2. MC TO BE SECURED/SUPPORTED A MAX 6' INTERVALS
3. MC TO SEAT ALL THE WAY IN CONNECTORS
11/01/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
10/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLANS SHOW RECEPTACLES IN EXAM ROOM (3 NEW) TO BE ON DEDICATED CKT
2. IDENTIFY NEW CKT IN PANEL DIRECTORY