Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : 1. MC TO BE SECURED WITHIN 12" OF ENCLOSURES/TERMINATIONS 2. MC TO BE SECURED/SUPPORTED A MAX 6' INTERVALS 3. MC TO SEAT ALL THE WAY IN CONNECTORS |
|
| 11/01/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 10/30/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLANS SHOW RECEPTACLES IN EXAM ROOM (3 NEW) TO BE ON DEDICATED CKT 2. IDENTIFY NEW CKT IN PANEL DIRECTORY |