Permit: T07CM03839

Parcel: 13322500E


Addresses:

7125 E BROADWAY BL

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
06/05/2008 FIRE - FINAL Approved
01/23/2008 FIRE - FINAL Not ready for Inspection NEED UP TO DATE FIRE SPRINKLER INSPECTION THIS DONE YEARLY, LAST ON FILE 05/04/2005.
NEED UP TO DATE FIRE ALARM CHECK VALVE INSPECTION THIS IS DONE EVERY 5 YEARS LAST ON FILE 11/1998.
NEED TO HAVE FIRE SPRINKLER SYSTEM ON A MONITORING SYSTEM 24 HOURS.