Permit: T07CM03835
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/02/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TUB VENT BEFORE GOING HORIZ. WITH VENT MUST BE SIX INCHES ABOVE FLOOD RIM OF FIXTURE THAT IT SERVES 2) SHOWER TRAP ARM CROWN VENTS NOT ALLOWED MAINTAIN 1/4" PITCH WIER TO VENT INLET 3) HOLES DRILLED IN FLOOR JOISTS, JOISTS ARE 13'-3" LONG BEARING TO BEARING 160", HOLES ARE NOT IN MIDDLE SPAN JUST MISSED BY 1" HOWEVER 2" MINIMUM DISTANCE IS REQUIRED FROM COMPRESSION OR TENSION EDGE. THESE HOLES THAT ARE NOT MORE THAN 2" FROM AN EDGE ARE NOTCHES, STARTING FROM THE EDGE TO THE BOTTOM OF THE HOLE, YOU ARE ALLOWED 1/6 THE DIMENSION OF THE JOIST. OVERNOTCHED CLAW FOOT TUB FULL OF H20 LOAD ? YOU NEED A FIX. I CANNOT TELL YOU HOW. |