Permit: T07CM03834

Parcel: 136310260


Addresses:

4675 S HARRISON RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM03834

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/07/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
TESTED DUCT SMOKE DETECTORS
OK FOR FINAL
AIR BALANCE OK
02/20/2008 MECHANICAL - FINAL Partial Approval STILL NEED TEST ON GAS PIPING
STILL NEED GFI ON ROOF
STILL NEED TO TEST DUCT SMOKE DETECTORS
02/13/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
LOW VOLTAGE WIRING NOT COMPLETE
UNITS NOT IDENTIFIED
CANVAS CONNECTOR STILL NOT COVERED ON 1 UNIT
NEED TO TEST DUCT SMOKE DETECTORS
PROVIDE GFI FOR CONDENSOR ON LOWER ROOF
02/08/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE MIN. R8 DUCT LINE IN ALL EXPOSED DUCT ON
THE ROOF. SECURE LOW VOLTAGE CONDUITS
ABOVE & BELOW ROOF
- HP-1 OVERFUSED
- PERMANENTLY ID UNITS
- INSTALL DUCT SMOKE DETECTORS IN RETURN DUCTS
- COVER SIDES OF CANVAS CONNECTORS BETWEEN DUCTS
- FINISH INSTALLING LOW VOLTAGE. USE PROPER CONNECTORS AT UNITS
- DO NOT SEAL ROOF JACKS WITH TAPE
- PROVIDE A GFI SERVICE RECEPTACLE ON ROOF AT EACH LEVEL WITH A WATERPROOF BUBBLE TYPE COVER
- CONDENSOR OVERFUSED
- PROVIDE OVERFLOW SENSOR ON FAN COIL
- NEED TO TEST DUCT SMOKE DETECTORS