Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM03834
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/07/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE TESTED DUCT SMOKE DETECTORS OK FOR FINAL AIR BALANCE OK |
|
02/20/2008 | MECHANICAL - FINAL | Partial Approval | STILL NEED TEST ON GAS PIPING STILL NEED GFI ON ROOF STILL NEED TO TEST DUCT SMOKE DETECTORS |
|
02/13/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* LOW VOLTAGE WIRING NOT COMPLETE UNITS NOT IDENTIFIED CANVAS CONNECTOR STILL NOT COVERED ON 1 UNIT NEED TO TEST DUCT SMOKE DETECTORS PROVIDE GFI FOR CONDENSOR ON LOWER ROOF |
|
02/08/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE MIN. R8 DUCT LINE IN ALL EXPOSED DUCT ON THE ROOF. SECURE LOW VOLTAGE CONDUITS ABOVE & BELOW ROOF - HP-1 OVERFUSED - PERMANENTLY ID UNITS - INSTALL DUCT SMOKE DETECTORS IN RETURN DUCTS - COVER SIDES OF CANVAS CONNECTORS BETWEEN DUCTS - FINISH INSTALLING LOW VOLTAGE. USE PROPER CONNECTORS AT UNITS - DO NOT SEAL ROOF JACKS WITH TAPE - PROVIDE A GFI SERVICE RECEPTACLE ON ROOF AT EACH LEVEL WITH A WATERPROOF BUBBLE TYPE COVER - CONDENSOR OVERFUSED - PROVIDE OVERFLOW SENSOR ON FAN COIL - NEED TO TEST DUCT SMOKE DETECTORS |