Permit: T07CM03815

Parcel: 136406750


Addresses:

9540 E 22ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03815

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/10/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/09/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
COMPLETE ITEMS #11 AND #12 FROM PREVIOUS INSPECTION
CHECK WITH BUILDING INSPECTOR FOR TCO
02/04/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MARK "SERVICE DISCONNECTS"
2. INSTALL BOX EXTENSION FOR SWITCHES IN TILE BOX MORE THAN 1/4" BACK
3. HAVE WIRES HANGING OUT AT CEILING
4. PLAN CALLS FOR 30a RECEPTS ON A19 & A21 HAVE 20 AMP RECEPTS ON 30a CIRCUITS
5. PLAN CALLS FOR 15a FUSES FOR AUTO LIFTS
6. NEED SERVICE RECEPT. WITHIN 25' OF AC UNIT
7. MOUNT PHONE 611 IN SEPARATE JUNCTION BOX
DO NOT WIRE THROUGH AC DISCONNECT
8. INSTALL 45a FUSES FOR AC UNIT
9. MISSING OUTDOOR EM LIGHT
10. PROVIDE HANDLE LOCK ON CIRCUIT B-16 AND B-24 PER PLANS
11. ALL RECEPTACLES IN SERVICE BAY TO BE GFI PROTECTED NEC 511.12
12. EM LIGHTING IN SHOP AREA TO MEET REQUIREMENTS OF NEC 700.16
13. ARE ALL METAL PIPING SYSTEMS BONDED?