Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/10/2009 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 01/26/2009 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) NEED TO POST BOND FOR POWER 2) MARK "SERVICE DISCONNECTS" 3) BOND METAL PIPING SYSTEMS AS DISCUSSED |
|
| 01/23/2009 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDING ELECTRODE CONDUCTOR TO TERMINATE @ NEUTRAL OR INSTALL JUMPER FROM NEUTRAL TO EQUIPMENT GROUND 2. BOND CT ENCLOSURE TO GROUNDED (NEUTRAL) CONDUCTOR 3. BOND GUTTER TO GROUNDED (NEUTRAL) CONDUCTOR 4. MARK "SERVICE DISCONNECTS" "1 OF 2" "2 OF 2" 5. PLAN CALLS FOR 3/0 CU FEEDERS TO PANELS 6. PLAN CALLS FOR PANELS TO BE MAIN BREAKER 7. NEED TO POST BOND 8. NEED TO BOND METAL PIPING SYSTEMS 9. OK DROP CEILINGS |
|
| 10/13/2008 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1. OK 4" SECONDARYS FROM SES TO CONNECTION @ STREET 2. OK 4" DATA ALSO |