Permit: T07CM03809

Parcel: 13305054L


Addresses:

8711 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T07CM03809

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/24/2009 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
08/21/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROVIDE LISTING AND INSTALL INSTRUCTIONS FOR DUCT SMOKE DETECTORS
2) INSPECTED ROOF TOP DUCTING-OK
07/01/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SUSPENDED ROUGH DUCT IN ATRIUM SOFFIT AND SHAFT OK TO COVER
2) CONFIRMED INSULATION INSIDE ROOF CURBS
3) 2" DUCT LINER OK ON EXPOSED DUCT
4) PROVIDE LETTER FROM ENGINEER
5) PROVIDE 1/8" PER FT. SLOPE ON ALL HORIZONTAL SECTIONS OF CONDENSATE DRAIN
06/10/2009 MECHANICAL - INTERMEDIATE Partial Approval 1ST FLOOR TO 26' CEILING - GRID LINE #1-4.2; SYSTEMS OK
DUCT WORKS IN PLACE
06/02/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
NOTE: PLANS INDICATE 1" DUCT BOARD ON EXTERIOR DUCT, EXTERIOR DUCT MUST HAVE A MINIMUM OF R-8 INSULATION, CORRECT ACCORDINGLY.

OK TO ROCK RESTROOM LIDS 1ST FLOOR MECHANICAL ONLY