Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T07CM03809
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2009 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/21/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PROVIDE LISTING AND INSTALL INSTRUCTIONS FOR DUCT SMOKE DETECTORS 2) INSPECTED ROOF TOP DUCTING-OK |
|
| 07/01/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SUSPENDED ROUGH DUCT IN ATRIUM SOFFIT AND SHAFT OK TO COVER 2) CONFIRMED INSULATION INSIDE ROOF CURBS 3) 2" DUCT LINER OK ON EXPOSED DUCT 4) PROVIDE LETTER FROM ENGINEER 5) PROVIDE 1/8" PER FT. SLOPE ON ALL HORIZONTAL SECTIONS OF CONDENSATE DRAIN |
|
| 06/10/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | 1ST FLOOR TO 26' CEILING - GRID LINE #1-4.2; SYSTEMS OK DUCT WORKS IN PLACE |
|
| 06/02/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NOTE: PLANS INDICATE 1" DUCT BOARD ON EXTERIOR DUCT, EXTERIOR DUCT MUST HAVE A MINIMUM OF R-8 INSULATION, CORRECT ACCORDINGLY. OK TO ROCK RESTROOM LIDS 1ST FLOOR MECHANICAL ONLY |