Permit: T07CM03808

Parcel: 112062360


Addresses:

2502 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03808

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/10/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/07/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL K.O BLANKS FOR HOLES IN HP1 & HP2 - NEC 110.12A
2. EMERGENCY LIGHTING NOT WIRED PER PLAN - NEC 700.12F
3. PANEL DIRECTORY NOT CORRECT - NEC 408.4
4. HAVE INSULATION UNDER GROUND SCREW TIME CLOCK J-BOXES - NEC 110.3B
5. OVERCURRENT PROTECTION FOR WATER HEATER TO HIGH
6. HAVE OVERFILLED J-BOXES -- NEC 314.16
7. HAVE OVERFILLED WIRE NUTS -- NEC 110.3 B
8. HAVE METAL J-BOXES THAT ARE NOT GROUNDED -
NEC 250.148
9. EMT TO BE SECURED (STRAP) WITHIN 36" OF ENCLOSURE
10. CHECK FOR PROPER BULB WATTAGE? - NEC 110.3B
03/06/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*