Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03808
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/10/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/07/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL K.O BLANKS FOR HOLES IN HP1 & HP2 - NEC 110.12A 2. EMERGENCY LIGHTING NOT WIRED PER PLAN - NEC 700.12F 3. PANEL DIRECTORY NOT CORRECT - NEC 408.4 4. HAVE INSULATION UNDER GROUND SCREW TIME CLOCK J-BOXES - NEC 110.3B 5. OVERCURRENT PROTECTION FOR WATER HEATER TO HIGH 6. HAVE OVERFILLED J-BOXES -- NEC 314.16 7. HAVE OVERFILLED WIRE NUTS -- NEC 110.3 B 8. HAVE METAL J-BOXES THAT ARE NOT GROUNDED - NEC 250.148 9. EMT TO BE SECURED (STRAP) WITHIN 36" OF ENCLOSURE 10. CHECK FOR PROPER BULB WATTAGE? - NEC 110.3B |
|
| 03/06/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |