Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T07CM03784
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/15/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
12/11/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WATER SUPPLY CONN. DRIPPING AT COMPRESSION FITTINGS 2. UNABLE TO LOCATE AIR GAP ON DRAIN CONNECTION 3. A DIRECT CONN. BETWEEN A POTABLE WATER SYSTEM AND A WASTE PIPE MAY NOT EXIST 4. CONTINUED DENIED INSP. WILL RESULT IN REINSPECTION FEES |
|
12/05/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* AG FOR RO NOT CORRECTED R.O WATER SUPPLY IS CONNECTED TO PROCESS/NON-POTABLE WATER SUPPLY TO ACORN VAC SYSTEM. REMOVE CONN. AND SUPPLY DRINKING WATER W/DOMESTIC WATER. CORRECT DRAIN. BACKFLOW CERT RECEIVED. |
|
12/02/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* BACKFLOW ASSEMBLY IS DRIPPING FROM CAP USE A CERTIFIED TESTER TO REPAIR AND TEST ASSEMBLY PROVIDE AN AIR GAP FITTING FOR DRAIN CONN. FROM WATER DISPENSING EQUIP. AT BR SINK. THIS IS A SERIOUS CROSS CONN. |
|
02/13/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* COMPLETE LIST FROM ABOVE NOTE: BACKFLOW ASSEMBLY IS LEAKING CONTINUED DENIED INSPECTIONS WILL RESULT IN REINSPECTION FEES |
|
12/20/2007 | PLUMBING - FINAL | Partial Approval | BACKFLOW CERT DOME STRAINER ABV CEILING SUPPORT CO PLUG AT 3-COMP SINK |
|
12/03/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - UNABLE TO LOCATE PLANS - LIST MAY NOT BE COMPLETE - PROVIDE PLAN REVISIONS REQUESTED ON 10/18 - FLOW CONTROL VENT NOT PROPERLY CONNECTED TO VENTING SYSTEM - SANITIZE COMP NOT INDIRECTLY PIPED - FS MISSING BASKET STRAINER - SANITIZER EQUIPT. NOT INSTALLED - ABV CEILING VENTS HAVE BACK PITCH - ABV CEILING VENTS NOT PROPERLY SUPPORTED - BACKFLOW PREVENTION ASSEMBLY NOT SUPPORTED AND MISSING UNION. PROVIDE CERT. - BREAKRM SINK MISSING CLIPS & CLEANOUT IS LEAKING AND HAS AN IMPROPERLY INSTALLED TRAP ARM. - WH PLATFORM NOT INSTALLED PER MANUFACTURES INSTRUCTIONS - EXP. TANK NOT SUPPORTED. T&P REQUIRES AG |