Permit: T07CM03784

Parcel: 12108001B

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/15/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
12/11/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WATER SUPPLY CONN. DRIPPING AT COMPRESSION FITTINGS
2. UNABLE TO LOCATE AIR GAP ON DRAIN CONNECTION
3. A DIRECT CONN. BETWEEN A POTABLE WATER SYSTEM
AND A WASTE PIPE MAY NOT EXIST
4. CONTINUED DENIED INSP. WILL RESULT IN
REINSPECTION FEES
12/05/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
AG FOR RO NOT CORRECTED

R.O WATER SUPPLY IS CONNECTED TO
PROCESS/NON-POTABLE WATER SUPPLY TO ACORN VAC SYSTEM. REMOVE CONN. AND SUPPLY DRINKING
WATER W/DOMESTIC WATER. CORRECT DRAIN.
BACKFLOW CERT RECEIVED.
12/02/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
BACKFLOW ASSEMBLY IS DRIPPING FROM CAP
USE A CERTIFIED TESTER TO REPAIR AND TEST ASSEMBLY
PROVIDE AN AIR GAP FITTING FOR DRAIN CONN. FROM WATER DISPENSING EQUIP. AT BR SINK. THIS IS A SERIOUS CROSS CONN.
02/13/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
COMPLETE LIST FROM ABOVE
NOTE: BACKFLOW ASSEMBLY IS LEAKING
CONTINUED DENIED INSPECTIONS WILL RESULT IN REINSPECTION FEES
12/20/2007 PLUMBING - FINAL Partial Approval BACKFLOW CERT
DOME STRAINER
ABV CEILING SUPPORT
CO PLUG AT 3-COMP SINK
12/03/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- UNABLE TO LOCATE PLANS
- LIST MAY NOT BE COMPLETE
- PROVIDE PLAN REVISIONS REQUESTED ON 10/18
- FLOW CONTROL VENT NOT PROPERLY CONNECTED TO VENTING SYSTEM
- SANITIZE COMP NOT INDIRECTLY PIPED
- FS MISSING BASKET STRAINER
- SANITIZER EQUIPT. NOT INSTALLED
- ABV CEILING VENTS HAVE BACK PITCH
- ABV CEILING VENTS NOT PROPERLY SUPPORTED
- BACKFLOW PREVENTION ASSEMBLY NOT SUPPORTED AND MISSING UNION. PROVIDE CERT.
- BREAKRM SINK MISSING CLIPS & CLEANOUT IS LEAKING AND HAS AN IMPROPERLY INSTALLED TRAP ARM.
- WH PLATFORM NOT INSTALLED PER MANUFACTURES INSTRUCTIONS
- EXP. TANK NOT SUPPORTED. T&P REQUIRES AG