Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T07CM03784
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/20/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/18/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO APPROVED HEALTH DEPT PLAN 2. 2-COMP OF 3 COMPARTMENT SINK WASH & RINSE TO BE DIRECTLY CONNECTED TO SANITARY DRAINAGE OR GREASE WASTE IF REQUIRED 3. SANITIZE BOWL OF 3-COMP SINK TO GO TO INDIRECT WASTE RECEPTOR 4. GREASE TRAP TO HAVE FULL SIZE DISCHARGE PIPING TO SANITARY DRAIN WITH FLOW CONTROL IN ACCESSIBLE LOCATION ON TAILPIECE OF FIXTURES BEING SERVED. 5. ALL PIPING TO BE TESTED 6. MOP SINK TO BE INSTALLED PER PLAN - PLEASE HAVE REDLINES ON SITE IF DEVIATION FROM PLAN IS REQUIRED. 7. PLEASE HAVE GREASE TRAP & FLOW CONTROL & GREASE WASTE PIPING REVISED TO MEET CHAPTER 10 UPC REQUIREMENTS WITH CITY APPROVAL. |