Permit: T07CM03784

Parcel: 12108001B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM03784

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/14/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
12/03/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
11/16/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. VDV CABLING TO BE SUPPORTED AS
PER 725.3 & 6, 800.3 & 6 300.11
2. ATTACH FIXTURES TO GRID - 410.16
3. FILL UNUSED OPENINGS IN BOXES
4. NEED SUPPORT WIRES FOR FIXTURES
5. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8
6. BOND GUTTER ENCLOSURE
7. VERIFY # OF CONDUCTOR FOR DERATING AT LARGE CONDUIT IN GUTTER 310.15 & 366.6
8. FILL UNUSED CONDUIT OPENINGS - 110.12

*MAINTAIN WORKING CLEARANCES AT PANEL AT ALL TIMES.