Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM03784
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/14/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
12/03/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
11/16/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. VDV CABLING TO BE SUPPORTED AS PER 725.3 & 6, 800.3 & 6 300.11 2. ATTACH FIXTURES TO GRID - 410.16 3. FILL UNUSED OPENINGS IN BOXES 4. NEED SUPPORT WIRES FOR FIXTURES 5. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8 6. BOND GUTTER ENCLOSURE 7. VERIFY # OF CONDUCTOR FOR DERATING AT LARGE CONDUIT IN GUTTER 310.15 & 366.6 8. FILL UNUSED CONDUIT OPENINGS - 110.12 *MAINTAIN WORKING CLEARANCES AT PANEL AT ALL TIMES. |