Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/17/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/16/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE NAIL PLATES ON MC CABLE THROUGH FURRING STRAPS HAVE LESS THAN 1 1/4" FROM FACE OF STUD TO CABLE 2. REMOVE CABLES FROM INSIDE FURRING CHANNELS OR PROVIDE PHYSICAL PROTECTION NEED 1 1/4" FROM FACE OF STUD TO WIRES RUN PARALLEL TO FRAMING MEMBERS 3. PLANS DO NOT ALLOW USE OF ROMEX CABLE 4. CABLES RUN PARALLEL WITH FRAMING MEMBERS REQUIRE 1 1/4" CLEARANCE TO FACE OF STUD 5. RECALL WHEN READY |