Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/17/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/16/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE NAIL PLATES ON MC CABLE THROUGH FURRING STRAPS HAVE LESS THAN 1 1/4" FROM FACE OF STUD TO CABLE
2. REMOVE CABLES FROM INSIDE FURRING CHANNELS OR PROVIDE PHYSICAL PROTECTION NEED 1 1/4" FROM FACE OF STUD TO WIRES RUN PARALLEL TO FRAMING MEMBERS
3. PLANS DO NOT ALLOW USE OF ROMEX CABLE
4. CABLES RUN PARALLEL WITH FRAMING MEMBERS
REQUIRE 1 1/4" CLEARANCE TO FACE OF STUD
5. RECALL WHEN READY