Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/15/2008 | FIRE - ALARM FINAL | Approved | SYSTEM APPROVED BY L.THOMAS | |
| 01/07/2008 | FIRE - ALARM FINAL | Denied | 1.) All classrooms shall have one door exiting to the outside, classroom #1 needs an exit door to the outside of the building or you will need to install a fire sprinkler system throughout the building. Need approved plans and permit before installing any doors. 2.) Occ. Load is over 50 therefore panic hardware is needed on rear door and main door. Numbers 120 and 101. 3.) Exit door in room #113 (office) needs to be outward or remove exit sign showing exit way. Plans shall be changed showing the removal of this exit. 4.) In room #113 (office) need to remove double cylinder keyed dead lock from door, need to have thumb style lock or no lock on door. |