Permit: T07CM03761

Parcel: 106011270


Addresses:

3775 N 1ST AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/07/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
01/03/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
SEAL ALL SCREWS ON TOP OF EXPOSED DUCT
VENTS WITHIN 10' OF AIR INTAKE MUST BE EXTENDED MIN. 3'
AIR BALANCE OK
12/31/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- OUTSIDE AIR FILTERS TO BE REMOVABLE AND SECURE INTO PLACE
- ALL LONG SEAMS ON EXTERIOR DUCT TO BE SEALED
- UNITS NOT PROPERLY LABELED
- ROOFTOP DUCT TO HAVE R-8 LINER (2")
- CONDENSATE ON UNIT 1 BROKEN AT UNIT
- REMOVE P-TRAP ON UNIT 2