Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2008 | MECHANICAL - INTERMEDIATE | Approved | ||
| 12/10/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 11/16/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - DO NOT USE TAPE TO SEAL DIRTY DUCT - COMBUSTIBLE MATERIAL NOT ALLOWED IN A RETURN PLENUM - SECTION 602.2.1 IMC - PROVIDE SCREWS IN EXHAUST DUCT CONNECTIONS - OK TO SHEETROCK RESTROOMS |