Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/31/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ROOF INSPECTION 1. SECURE EMT TO ROOFTOP - NEC 110.13B 2. IDENTIFY EQUIPMENT - NEC 110 3. STRAP FLEX WITHIN 12" OF TERMINATIONS INSIDE 1. IDENTIFY SERVICE DISCONNECTS 2. NEED 1/0 BOND TO WATER/GAS - NEC 250.66 3. EMERGENCY LIGHTING TO BE PER NEC 700.12 AND AIM SO IT IS EFFECTIVE 4. REVISE PANEL DIRECTORY - NEC 408.4 5. FIREALARM DEVICES TO BE PER PLAN |