Permit: T07CM03761

Parcel: 106011270


Addresses:

3775 N 1ST AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/31/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/28/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ROOF INSPECTION
1. SECURE EMT TO ROOFTOP - NEC 110.13B
2. IDENTIFY EQUIPMENT - NEC 110
3. STRAP FLEX WITHIN 12" OF TERMINATIONS

INSIDE
1. IDENTIFY SERVICE DISCONNECTS
2. NEED 1/0 BOND TO WATER/GAS - NEC 250.66
3. EMERGENCY LIGHTING TO BE PER NEC 700.12 AND AIM SO IT IS EFFECTIVE
4. REVISE PANEL DIRECTORY - NEC 408.4
5. FIREALARM DEVICES TO BE PER PLAN