Permit: T07CM03755

Parcel: 10714376C


Addresses:

555 E GRANT RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T07CM03755

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/02/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
05/29/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :$
CONSTRUCTION TRAILER GONE, NO CONTRACTORS LOCATED
WITHIN STORE, STORE EMPLOYEES HAD NO IDEA WHERE TO LOCATE CONTRACTOR, PROVIDE CONTACT NUMBERS AND HAVE MECHANICAL CONTRACTOR ON SITE WITH LADDERS TO INSPECT DAMPERS
05/01/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
ALL DAMPERS NOT INSTALLED
04/24/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
CHECKED WRAPPED SUPPLY DUCT TO RESTROOMS
04/14/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
- SUPPLY DUCT TO RESTROOMS TO BE WRAPPED
- HVAC CONTRACTOR TO BE PRESENT AT FIRE DAMPER INSPECTION
03/19/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
BREAKROOM OK FOR TILES ON MECHANICAL ONLY
03/17/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
03/06/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PROVIDE SHEETMETAL STAMPS ON REC. DUCT AND ROUND DUCT OVER 10" DIAMETER
OK TO INSULATE DUCT