Permit: T07CM03755

Parcel: 10714376C


Addresses:

555 E GRANT RD


Inspection Status: Partial Approval

Inspection History: PLUMBING - FINAL

Permit Number - T07CM03755

Inspection Description - PLUMBING - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
05/20/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
BEVERAGE CENTER AT THE END OF THE DELI INSTALLED OK
CERTIFICATIONS ON FILE
FOR FINAL - PROVIDE REVISED APPROVED PLAN AND HAVE REDLINES AVAILABLE FOR COMPARISON
05/16/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. DELI FINAL OK
2. BAKERY FINAL OK
3. PRODUCE FINAL OK SUBJECT TO HEALTH DEPT. APPROVAL OF HAND SINK
04/04/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
WOMENS RESTROOM COMPLETE
03/31/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
FLOOR SINKS AT MEAT CASE COMPLETE
OK FOR CONCRETE
OK TO COVER FLOOR AND WALLS AT MENS RESTROOM
03/26/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. CORRECTIONS IN FLORAL MADE OK
2. MEAT CASES DRAIN TIE IN OK
HORIZONTAL VENTS BREAK TO WALL OK
FLOOR SINKS (3) ADJUSTED FOR CORRECT ROUGH IN PER KEYNOTE #9
3. OK TO COVER U.G AT SERVICE CENTER FOR FUNNEL DRAIN
4. FLOOR SINKS ADJACENT TO COLUMN LINE 3.0 ADJUSTED AS REQUIRED BY KEYNOTE #19
03/25/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
03/24/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
03/20/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. MENS RESTROOM LAVATORIES ONLY UNDERGROUND
OK TO COVER
2. HARD PIPE, FULL SIZE (1/2") TO RPPBP - FIXTURE CONNECTOR NOT APPROVED
3. REMOVE RAISED SQUARE HEAD PLUG. INSTALL COUNTER SUNK, TAPPED, CLEANOUT PLUG W/CHROME COVER
4. INSTALL STRAINER AT FLOOR SINK. SINK MAY NOT BE CONSIDERED "ACCESSIBLE"
03/17/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
PHARMACY SINK OK

FLORAL SINK SPRAYER REQUIRES CORRECT BACKFLOW PROTECTION AND ACCESS TO FLOOR SINK
02/15/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
FAMILY RESTROOM 119 OK