Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
05/16/2008 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
05/02/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
TIE IN FOR G.W AT WEST SIDE EXTERIOR AND NORTHSIDE EXTERIOR WITH VENT OK
04/30/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
GREASE WASTE IN BAKERY/DELI AREA - OK TO COVER
INTERCEPTOR SET OK TO COVER
INLET, OUTLET AND VENT OK
04/28/2008 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
04/25/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
- 4" SANITARY SEWER FROM PUBLIC CONNECTION BACK TO 3' INSIDE LOT WALL WATER TEST OK
- 4" GW FROM CONTINUATION THRU CLEANOUT APP. 60' EAST TOWARD INTERCEPTOR LOCATION TEST OK FOR PIPING
APP. 20' WEST OF INTERCEPTOR
04/24/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. FIRST HUNDRED FEET OF 4" SCH 40 ABS TO CROSSING OK
TO COVER. TESTED AT 5 POUNDS.
2. 3" GREASE WASTE AND VENT. FIRST 80' FROM BLDG.
OK TO COVER
04/18/2008 PLUMBING - ROUGH, SOIL Partial Approval - MENS RESTROOM FINAL OK
- 3 FLOOR SINKS AT DELI OK
- ISLAND PRODUCE HAS A WATER SUPPLY
04/08/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
THREE FLOOR SINKS AT GROCERY FREEZER ADJUSTED OK
OK TO COVER
03/31/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
03/26/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
03/25/2008 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
03/24/2008 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
03/20/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
03/05/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
TWO FLOOR SINKS IN BAKERY OK TO COVER
PIPE WRAPS ALONG COLUMN #3 OK
03/04/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
- VTR'S ALONG COLUMN #3 OK TO COVER
- IT DOESN'T LOOK LIKE THE PIPE GOT WRAPPED THRU THE FLOOR - RECALL INSPECTION FOR WRAP VERIFICATION.
- CLOSET FLANGES AT LADIES RESTROOM NEXT TO
PHARMACY OK
02/28/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
THREE FLOOR SINKS NEXT TO COLUMN #3 UNDERGROUND
OK TO COVER. WATER TEST TO TEN FEET. PIPING UP TO TEN FEET
02/25/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
ABS DWV AT FLORAL THRU ROOF OK
COLD SUPPLY OK
OK TO COVER WALLS AND CEILING THIS AREA ONLY
02/21/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
WATER TEST PAGE P1
3-FLOOR SINKS PER REDLINE P.4 INITIALED ON P.1
02/15/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
FLORAL 101 - FLOOR SINK & FLOOR SINK UNDERGROUND PER REDLINE ON SITE WATER TEST OK
02/13/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
LADIES RESTROOM NEXT TO PHARMACY OK TO COVER
WALLS AND OVERHEAD. NEED TO SEE FLANGES SECURED.
02/08/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
DELETED CLEANOUTS CAPPED OFF OK AT BAKERY
OK FLOOR SINK IN BAKERY - OK TO COVER
FLOOR SINK TRAP ARM EXTENDED TO OUTSIDE WALL
WILL CONTINUE AT A LATER DATE
02/05/2008 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) NOT INSTALLED PER PLAN
2) NO RED LINES ON PLAN
3) PART OF UNDERFLOOR COVERED BY PLYWOOD
02/05/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. FAMILY RESTROOM - OK TO COVER UP TO MEZZANINE FLANGE OK
2. PHARMACY OK TO COVER - REDLINE ALL CHANGES TO PLAN
01/30/2008 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
01/29/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
NEW PHARMACY SE CORNER 208-484-6520

WASTE & VENT THRU ROOF AT PHARMACY SINK OK TO COVER AFTER INSTALLING FOAM WRAPS AT CONCRETE PENETRATION
DOMESTIC WATER ALSO, OK
01/23/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
- FAMILY RESTROOM INSTALLED PER REDLINE
- ADDITIONAL FLOOR DRAIN TO BE INCORPORATED IN FUTURE PLAN REVISION.
- OK TO COVER SUBJECT TO REVISED APPROVED PLAN
- WATER TEST ONE RISER TO TEN FEET
01/22/2008 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. CITY CONDUCTS INSPECTIONS BETWEEN 7:00-3:30 DAILY
2. PLANS AND PERMITS ARE TO BE AVAILABLE
3. CONTINUE LEAVING MESSAGES
01/18/2008 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. UNABLE TO LOCATE PERMIT OR APPROVED PLAN
2. ON PLUMBING PLAN - FLOOR DRAINS REDLINED ON PLAN WILL REQUIRE APPROVED REVISION
3. LEAVE A NAME AND CONTACT NUMBER WHEN SCHEDULING THIS INSPECTION.