Permit: T07CM03755

Parcel: 10714376C


Addresses:

555 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03755

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/24/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/09/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
03/20/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/20/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
RECEIVED MONEY ORDER 09-086344332 ----- $150.00
THESE ARE LAST ITEMS

PHARMACY:
FINISH #1 & 4
STORE ABOVE CEILING
1. SUPPORT M/C CABLES LAYING ON GRID
2. SUPPORT VDV CABLING LAYING ON GRID
3. EXPOSED CONDUCTORS - REMOVE TO LAST BOX

OK 2X4's AT CASHIER
OK BATHROOM EM LIGHT
OK REFRIGERATION CASES
OK ROOF
OK DELI CASES

DELI:
1. TRANSFORMER GROUNDING ELECTRODE CONDUCTOR 250.64(E)
2. BOND AT CONCENTRICS ABOVE 250V 250.97 XFMR "TL" DISCONNECT
3. TIGHTEN LOOSE FITTINGS
4. PROTECT CONDUCTORS PNL "TL"
5. SUPPORT FEEDER CONDUIT ( 1 - 1/4") TO RAN WASHER
10' INTERVALS
6. LABEL CIRCUIT DIRECTORIES 408.4 - NO ABBREVIATIONS
7. GRAY CANNOT BE USED FOR UNGROUNDED CONDUCTOR 200.7

TRAC LIGHTS:
1. FINISH SUPPORTING 1 PER 4'
03/18/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK EM LIGHTING EXCEPT AS NOTED

1. MENS RESTROOM EM LIGHT NOT WORKING
2. SECURE 2X4's TO GRID - 410.16
3. UNUSED BOXES ABOVE CEILING
4. SUPPORT MC ABOVE CEILING
5. SUPPORT VDV CABLING ABOVE CEILING
6. SUPPORT TRAC LIGHTS 1 PER 4' FROM STRUCTURE
7. FIXTURE NOT FOR JUNCTION BOX - 2X4
8. M/C TO TERMINATE
9. FILL UNUSED OPENINGS AND MISSING COVERS

RECEIVED MONEY ORDER #09-086343875 -- $150.00
03/18/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
UPSTAIRS ELECTRIC EQUIPMENT:
1. GROUNDING ELECTRODE BOND PER 250.64(E)
2. TIGHTEN LOOSE FITTINGS
3. MAINTAIN WORKING CLEARANCES
4. LABEL EQUIPMENT
5. ONLY ONE CONDUCTOR TO GROUND LUG
6. DEFROST EQUIPMENT NOT AS PER PLANS
7. MOUNT DISCONNECTS VERTICAL OR CHANGE
TO GUTTER/JUNCTION BOX
8. NEED ILLUMINATION AT PANELS LPCS2 AND LPAP2

DELI PREP:
1. MAINTAIN WORKING CLEARANCES
2. DISHWASHER DISCONNECT - PROTECT CONDUCTORS 300.4
ONE WIRE PER LUG, CLEAN SURFACE UNDER LUG 250.12
NO SHEETMETAL THREAD 250.8, CLEARANCES 110.26
03/17/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
PHARMACY:
1. EQUIPMENT GROUNDING CONDUCTOR TO BE GREEN ENTIRE LENGTH 250.119
2. SECURE FIXTURES TO GRID -- 410.16
3. SUPPORT M/C CABLE 12" AND 6' AS PER CODES
4. SUPPORT VDV CABLING 725.24, 800.24, 300.11
5. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8
SUPPORT BOX NOT LAYING ON TILE
6. BOXES MORE THAN 1/4" NON-COMBUSTIBLES OR FLUSH COMBUSTIBLES - 314.20

ALL PLAN REVISIONS TO BE ON SAME ELECTRICAL PAGE FOR LIGHTING E-2

ABOVE CEILING CARD RACKS:
1. SUPPORT M/C CABLES AS PER CODES
2. GROUND JUNCTION BOXES
3. FILL UNUSED OPENINGS IN BOXES - OPEN BOXES WITH EXPOSED CONDUCTORS
4. M/C TO TERMINATE WITH AN APPROVED FITTING
5. SUPPORT VDV CABLING
01/21/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
MEET WITH CONTRACTOR TO DISCUSS
PROJECT & SCHEDULING
06/03/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
06/03/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. LIGHTING NOT AS PER PLANS FOR EM LIGHTS
- PANEL LPEM & CP RECEPTACLES WORK AS PLANS
- CENTER ROW OF EM LIGHTS MISSING OR NOT WORKING/MAIN SALES
- LIGHT IN FRONT OF PHARMACY MISSING OR NOT WORKING
- DELI & CHECK STAND 2X4's NOT AS PLANS
- OUTSIDE "2" FIXTURES MISSING

*THIS INSPECTION WAS FOR EM LIGHTS & CIRCUITS TO WORKING CONDITIONS ONLY

RECEIVED MONEY ORDER #08-905634550 FOR $150.00
06/02/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR EMERGENCY LIGHTING ONLY

1. EMERGENCY LIGHTING NOT WORKING/NOT PER PLAN
REVISED ELECTRICAL PLAN NOT ON SITE YET.
2. GO THROUGH ALL EMERGENCY LOADS TO CHECK FOR PROPER OPERATION & PER APPROVED REVISED PLAN
05/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR ROOFTOP
1. NEED SERVICE RECEPTACLE WITHIN 25' OF UNIT
2. SECURE ALL EQUIPMENT TO STRUCTURE
3. IDENTIFY DISCONNECT
4. STRAP FLEX
5. STAT WIRE TO BE IN RACEWAY INTO UNIT
6. IDENTIFY HOOD MOTOR DISCONNECT
7. SEAL OFF ROOF PENETRATIONS
05/22/2008 ELECTRIC - FINAL Cancelled IVRS - RI canceled
05/01/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK MENS BATHROOM BY PHARMACY, EMERGENCY LIGHTING ETC. STILL TO BE CHECKED.
2. OK WALL COVER ECR ROOM
3. NEW SINK NEXT TO HOOD IN DELI PREP AREA NOT TO BLOCK WORKING CLEARANCES FOR EXISTING EQUIPMENT (NEC 110.26) RELOCATE EQUIPMENT AS NEEDED.
04/30/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
04/21/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FLORAL AREA
ALSO LOOKED AT MEAT TERMINATIONS
04/11/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
INSPECTION FOR CUSTOMER SERVICE COUNTER RECEPTACLES

1. ISOLATED EQUIPMENT GROUNDING CONDUCTORS ARE TO BE PROPERLY IDENTIFIED - NEC 250.119, HERE AND THROUGHOUT PROJECT.

OK CUSTOMER SERVICE COUNTER AFTER CORRECTIONS
04/10/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELED
04/07/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK USE OF WOMENS RESTROOM BEHIND PHARMACY
03/26/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
1. TRANSFORMER SECONDARY CONDUCTORS FEEDING DEFROST PANEL TO HAVE DISCONNECT/OVERCURRENT PROTECTION WITHIN 10' -- SEE PLAN AND NEC 240.21C
2. TRANSFORMER TO BE GROUNDED PER 250.30 A7 - IS STEEL BONDED TO SERVICE? ALUMINUM LUG NOT USED AS LISTED
NEC 110.3B
3. PROVIDE ILLUMINATION FOR NEW EQUIPMENT - 110.26D
4. PROVIDE IDENTIFICATION FOR TRANSFORMER AND DEFROST PANEL AT MDS DISCONNECT - NEC 110
5. TRANSFORMER TO HAVE MINIMUM 6" BACK CLEARANCE
NEC 110.3B
6. ALL EQUIPMENT TO HAVE PROPER WORKING CLEARANCE
NEC 110.26
7. NEW REMOTE DEFROST PANEL EQUIPMENT TO BE INSPECTED DISCONNECT 45KVA TRANSFORMER AND PANEL

FLORAL AREA OCCUPIED BEFORE INSPECTION/APPROVAL
CONNECTIONS FOR CASES TO BE OPEN FOR INSPECTION
03/24/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
- OK AUTOMATIC DOOR ROUGH #2
- OK BREAKROOM TCO SUBJECT TO BLD. INSP.
- OK MNGR. OFFICE TCO SUBJECT TO BLD. INSP.
- DO NOT USE THE NEUTRAL BAR AS A GROUND TAP BAR IN 75KVA X-FORMER
03/19/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/18/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
03/18/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
BILL @ 208-362-3040

INSPECTION FOR PHARMACY AREA ONLY
1. NEED EXTENDERS FOR BOXES SET BACK MORE THAN 1/4" (NOT CUT IN MUD RINGS)
2. HAVE ISOLATED GROUND RECEPTACLES SHOWING OPEN GROUND
3. RECEPTACLES TO SEAT FIRMLY IN BOX AND NOT LOOSE OR SET BACK FROM FACE PLATE
4. PANELS WITH CKT'S THAT FEED THIS AREA TO BE OPEN FOR INSPECTION
5. NEED TO CONDUCT EMERGENCY LIGHT TEST FOR THIS AREA

PARTIAL INSPECTION ONLY ELECTRICIAN TO BE ON SITE
ALL EQUIPMENT TO BE ACCESSIBLE
THIS AREA IS NOT TO BE OCCUPIED
03/17/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/10/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FAMILY RESTROOM