Permit: T07CM03753

Parcel: 114540640

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/28/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
SUPPORT 1/2 INDIRECT DRAIN FROM ESPRESSO W/APPROVED
PIPE CLAMPS. CORRECT DIP IN DRAIN HOSE. PROVIDE SLOPE THROUGHOUT
05/23/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1. NEED COPIES OF YOUR INTERNAL BACKFLOW ASSEMBLY CERTIFICATIONS AND BACTERIA REPORT.
2. HARD PIPE BACKFLOW AT COFFEE; CONNECT DRAIN AND WATER TO ESPRESSO MACHINE
3. SEAL CO PLUGS
4. SUPPORT AND ENSURE 1" AG AT ID WASTE
5. SUPPORT ID WASTES FROM SODA
05/21/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- COMPLETE PREVIOUSLY NOTED ITEMS.
- CLEANOUTS, PRIMER, TRAPS
- AG PROPER USE OF DRAINAGE FITTINGS ON ID WASTES
- CORRECT LEAKS
- HARD PIPE TO BACKFLOW ASSEMBLIES AT COFFEE & ESPRESSO
- EXTEND VENT TO 3' ABV AIR INTAKE
- PROTECT FROM UV RAYS
05/20/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
05/15/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- COMPLETE ALL WORK, INSTALL ALL EQUIPMENT THAT HAS WATER AND DRAIN CONNECTIONS
- PROVIDE BACTERIA REPORT AND BACKFLOW CERTS
- PROVIDE ACCESS TO ALL CLEANOUTS
- PROVIDE VAC BREAKERS ON EXTERIOR HOSE CONNECTIONS
- PROVIDE ACCESS TO ROOF
- PROPERLY INSTALL SINKS
- CAULK ALL FIXTURES
- CORRECTLY INSTALL ALL INDIRECT WASTE PIPING;
CLEANOUTS, PVC PRIMER, PROPER SUPPORTS, TRAPS AS REQUIRED, SLOPE;
ID PIPING CANNOT COMBINE
SEE UPC CHPT. 8 801, 803
05/13/2008 PLUMBING - FINAL Cancelled CANCELED PER WAYNE
240-1845