Permit: T07CM03753

Parcel: 114540640

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/06/2008 ELECTRIC - FINAL Approved REVISIONS OK
05/30/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK BREAKER
REVIEWED REDLINES
05/28/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. ICE MAKER INSTRUCTIONS SAY 15 AMP MAX FUSE OR BREAKER
2. FINISH AS BUILT DRAWINGS AS DISCUSSED WITH WAYNE
05/23/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
1. FINISH #1 & #3
2. PLEASE PROVIDE A LADDER FOR ROOF ACCESS

PLEASE PAY REFEE BEFORE NEXT INSPECTION
05/21/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PLEASE VERIFY LISTING FOR ICE MACHINE AND HOW IS POWER CONNECTED
2. FINISH PREVIOUS ITEMS 1, 3, 8, 9

ROOF:
1. MAINTENANCE RECEPTACLE COVER BROKEN
2. USE APPROVED FITTING FOR A/C UNIT
3. LABEL DISCONNECT
05/09/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
*CK ROOF NEXT TIME

1. EXTENDER RINGS NEEDED AT COMBUSTIBLES OR MORE THAN 1/4" ON NON-COMBUSTIBLES
2. USE APPROVED HARDWARE WITH DEVICES
3. COUNTER RECEPTACLES NOT AS PLANS - LAYOUT & GFCI'S
4. SPLIT BOLTS LISTED FOR 2 CONDUCTORS ONLY -
A RUN AND A TAP
5. OPEN JUNCTION BOXES
6. ATTACH FIXTURES TO GRIDS
7. PANEL "L" NOT RATED AT 22,000 AS PER PLANS
8. LABEL OUTSIDE OF PANEL COVERS
9. PLANS CALL FOR ALL, INCLUDING LOW VOLTAGE WIRING TO BE IN CONDUIT
10. NEED TO SEE THE REST OF THE EQUIPMENT TO VERIFY LISTINGS
11. HALL EM LIGHT NOT ON CIRCUIT