Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2008 | ELECTRIC - FINAL | Approved | REVISIONS OK | |
| 05/30/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK BREAKER REVIEWED REDLINES |
|
| 05/28/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. ICE MAKER INSTRUCTIONS SAY 15 AMP MAX FUSE OR BREAKER 2. FINISH AS BUILT DRAWINGS AS DISCUSSED WITH WAYNE |
|
| 05/23/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio 1. FINISH #1 & #3 2. PLEASE PROVIDE A LADDER FOR ROOF ACCESS PLEASE PAY REFEE BEFORE NEXT INSPECTION |
|
| 05/21/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PLEASE VERIFY LISTING FOR ICE MACHINE AND HOW IS POWER CONNECTED 2. FINISH PREVIOUS ITEMS 1, 3, 8, 9 ROOF: 1. MAINTENANCE RECEPTACLE COVER BROKEN 2. USE APPROVED FITTING FOR A/C UNIT 3. LABEL DISCONNECT |
|
| 05/09/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* *CK ROOF NEXT TIME 1. EXTENDER RINGS NEEDED AT COMBUSTIBLES OR MORE THAN 1/4" ON NON-COMBUSTIBLES 2. USE APPROVED HARDWARE WITH DEVICES 3. COUNTER RECEPTACLES NOT AS PLANS - LAYOUT & GFCI'S 4. SPLIT BOLTS LISTED FOR 2 CONDUCTORS ONLY - A RUN AND A TAP 5. OPEN JUNCTION BOXES 6. ATTACH FIXTURES TO GRIDS 7. PANEL "L" NOT RATED AT 22,000 AS PER PLANS 8. LABEL OUTSIDE OF PANEL COVERS 9. PLANS CALL FOR ALL, INCLUDING LOW VOLTAGE WIRING TO BE IN CONDUIT 10. NEED TO SEE THE REST OF THE EQUIPMENT TO VERIFY LISTINGS 11. HALL EM LIGHT NOT ON CIRCUIT |