Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2008 | ELECTRIC - ABOVE CEILING | Approved | ||
| 04/09/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE |
|
| 04/07/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ALL LIGHTS NEED SUPPORT WIRE 2. ELECTRICAL TO BE SUPPORTED AS PER 300.11 |
|
| 03/24/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK FRONT LINE WEST OK BATHROOMS *725.6, 800.3 & 24, 300.11 WILL APPLY TO VDV CABLING |
|
| 03/21/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT MC CABLES AS PER 330.30 2. JUNCTION BOXES TO BE ACCESSIBLE 3. NO MORE THAN 360 DEG. IN CONDUIT RUNS |