Permit: T07CM03748

Parcel: 108240800


Addresses:

2502 E RIVER RD


Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T07CM03748

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
01/08/2008 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
01/07/2008 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
NOT ACCESSIBLE DUE TO STUCCO
01/04/2008 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUNDING ELECTRODE CONDUCTOR TO CONNECT DIRECTLY TO SERVICE NEUTRAL OR VIA A MAIN BONDING JUMPER
2. USE CORRECT SIZED PIPE CLAMPS AND TIGHTEN
3. IDENTIFY "SERVICE DISCONNECTS" AS SUCH
4. TIGHTEN ALL CONNECTIONS
5. ARRANCE BONDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT
12/28/2007 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :
STILL WAITING FOR REVISED SINGLE LINE DIAGRAM
12/27/2007 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
1) APPROVED PLANS TO BE ON SITE
12/24/2007 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*