Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM03748
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/25/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 01/24/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PANEL DIRECTORIES TO BE AS PER 408.4 2. OFFICE FURNITURE TO BE AS PER 605.7 AND WE NEED TO SEE CONNECTIONS 3. PROTECT SEAL TITE FROM SHARP METAL EDGES AT EXHAUST HOOD. |
|
| 11/13/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK DRYWALL-NEED TO CHECK 1, 2 AND 4 |
|
| 11/07/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EQUIPMENT GROUNDS TO WRAP MINIMUM 2/3RDS AROUND GROUND SCREWS AND TIGHTEN ALL METAL BOXES TO BE GROUNDED 2. IDENTIFY WHITE USED AS HOT 3. NEED NAIL PLATES FOR MC WHERE HOLE IS LESS THAN 1 1/4" FROM STUD FACE 4. SUPPORT BRACKETS TO BE BENT TO PROPER DEPTH 5. PLANS TO BE REVISED TO CORRECT LINE/ DIAGRAM /PANEL LOCATIONS 6. PLANS CALL FOR RACEWAYS AND BOXES FOR DATA |