Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03742

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/14/2007 ELECTRIC - FINAL Approved
12/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ABOVE WALK IN
1. SEAL INTERIOR OF ALL RACEWAYS INTO WALK IN -
NEC 300.7
2. STRAP FLEX WITHIN 12" OF ENCLOSURES - NEC 348.30

IN WALK IN
1. PROVIDE DISCONNECTING MEANS FOR FAN COIL -
NEC 440.14

TRANSFORMER:
1. SECONDARY CONDUCTORS TO BE NO MORE THAN 25' LONG WITHOUT OVERCURRENT PROTECTION - NEC 240.21C
2. FLEX TO BE SECURED WITHIN 4' OF TRANSFORMER -
NEC 348.30
3. GROUNDING ELECTRODE CONDUCTOR TO BE NEAR TRANSFORMER - CLOSEST AVAILABLE -
1. WATER PIPE OR
2. BUILDING STEEL - DO NOT RUN ACROSS CEILING - NEC 250.30 A7
12/12/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO INSPECTION AT THIS TIME

NOTE: TRANSFORMER SECONDARY BONDING CONDUCTOR TO BE PER NEC 250.30.2
TRANSFORMER FEEDER EQUIPMENT GROUND UNDERSIZED - NEC 250.122 B
12/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TRANSFORMER (75 KWA) NOT TO BE INSTALLED IN CEILING
NEC 450.13 B, NO FURTHER INSPECTION OF TRANSFORMER AT THIS TIME
2. PROVIDE INTERLOCK WIRING DIAGRAM FROM ELECTRICAL ENGINEER FOR PROPER SEQUENCE OF OPERATION OF
TYPE 1 HOOD
3. WIRING FOR WALK IN CONDENSOR AND FAN COIL NOT SHOWN ON PLAN - REVISE AS NEEDED - NO FURTHER INSPECTION OF WALK-IN AT THIS TIME
4. REMOVE ALL TEMPORARY LIGHTING FROM CEILING
5. DEMO/REMOVE ALL UNUSED EQUIPMENT IN CEILING
6. SECURE LIGHT FIXTURES TO GRID - NEC 300.11
7. MC TO BE SUPPORTED/SECURED WITH 12" OF TERMINATIONS AND MAX 6' INTERVALS - NEC 330.30
8. SUPPORT WIRES FOR EQUIPMENT TO BE SECURED @ BOTH ENDS - NEC 300.16
9. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES -
NEC 358.30
10. CHECK BOX FILL & GROUNDING - NEC 314.16

PARTIAL INSPECTION ONLY