Permit: T07CM03740

Parcel: 10605005E


Addresses:

3817 N ORACLE RD A


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03740

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/09/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED PROPER TYPE MC CONNECTORS FOR MC - NOT ROMEX CONNECTORS
2. GROUND ALL METAL J-BOXES
3. SUPPORT WIRES FOR MC TO BE SECURED AT BOTH ENDS
TIE LOOSE ENDS TO GRID
4. ALL FIXTURES TO BE PROPERLY GROUNDED WITH EQUIPMENT GROUNDING CONDUCTOR
5. HAVE OVERFILLED J-BOXES
6. REFEE IF ALL NOT CORRECT NEXT INSP.
12/19/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
12/12/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
A LADDER IS NEEDED FOR INSPECTION
ALL WORK TO BE DONE BY LICENSED ELECTRICAL CONTRACTOR - PROVIDE CONTRACTOR NAME & PHONE #
11/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ROMEX NOT ALLOWED ABOVE SUSPENDED CEILING
2. HAVE OPEN WIRING THROUGH CEILING TO TRACK LIGHTING
3. INSTALL ALL DEVICES & COVERS
4. HAVE BROKEN BREAKER HANDLE IN PANEL
5. ALL PAINTED OVER DEVICES TO BE REPLACED
6. SECURE LOOSE RECEPTACLES IN WALLS
7. PROVIDE GFI PROTECTION FOR BATH RECEPTACLE
8. ALL WIRING/RACEWAYS ABOVE CEILING TO BE PROPERLY SUPPORTED/CLOSED OFF - REMOVE UNUSED LIGHTING FIXTURES.