Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03740
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/09/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED PROPER TYPE MC CONNECTORS FOR MC - NOT ROMEX CONNECTORS 2. GROUND ALL METAL J-BOXES 3. SUPPORT WIRES FOR MC TO BE SECURED AT BOTH ENDS TIE LOOSE ENDS TO GRID 4. ALL FIXTURES TO BE PROPERLY GROUNDED WITH EQUIPMENT GROUNDING CONDUCTOR 5. HAVE OVERFILLED J-BOXES 6. REFEE IF ALL NOT CORRECT NEXT INSP. |
|
12/19/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
12/12/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* A LADDER IS NEEDED FOR INSPECTION ALL WORK TO BE DONE BY LICENSED ELECTRICAL CONTRACTOR - PROVIDE CONTRACTOR NAME & PHONE # |
|
11/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ROMEX NOT ALLOWED ABOVE SUSPENDED CEILING 2. HAVE OPEN WIRING THROUGH CEILING TO TRACK LIGHTING 3. INSTALL ALL DEVICES & COVERS 4. HAVE BROKEN BREAKER HANDLE IN PANEL 5. ALL PAINTED OVER DEVICES TO BE REPLACED 6. SECURE LOOSE RECEPTACLES IN WALLS 7. PROVIDE GFI PROTECTION FOR BATH RECEPTACLE 8. ALL WIRING/RACEWAYS ABOVE CEILING TO BE PROPERLY SUPPORTED/CLOSED OFF - REMOVE UNUSED LIGHTING FIXTURES. |