Permit: T07CM03725

Parcel: 115180050


Addresses:

1601 N ORACLE RD 05

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/28/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/24/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SCREWS ARE NOT ALLOWED ON B-VENT PIPING WHERE THEY PENETRATE INNER LINER. PER MANUFACTURES INSTRUCTIONS.
2. B-VENT PIPING MUST BE A MINIMUM OF 1" AWAY FROM
ANY AND ALL COMBUSTIBLE MATERIAL INCLUDING
SHEETROCK PER IMC
08/08/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*