Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T07CM03722
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/25/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* REVISED DELTA 3 PLAN ON SITE DATED 1/23/08 WAITING ON PLAN CHECK STAMP |
|
01/23/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
01/14/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 4" CONTINUATION OF BUILDING DRAIN AND SEWER WITH BACKWATER VALVE WATER TEST OK SHALL PROVIDE VENT FOR SEWER PER 904.1 AND CITY APPROVED SITE PLAN (PROVIDE TRACER WIRE ON EXTERIOR PRIOR TO COVERING) |
|
01/09/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
12/06/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DWV WATER TEST THRU ROOF OK WATER PIPING IN WALL & OVERHEAD TEST OK 1. SHALL SEE COMPLETION OF 1 1/2 TO METER FROM BUILDING INTERIOR AND INSULATION OVERHEAD. REVISED CITY APPROVED PLANS REQUIRED FOR FINAL |