Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03722
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/28/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* STILL NEED APPROVED REVISION FOR SERVICE |
|
01/25/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* EM LIGHTING NOT PER PLAN |
|
01/24/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. INSTALL HOSPITAL GRADE RECEPTACLES AS DISCUSSED 2. INSTALL EXTENSIONS ON RECEPTACLES IN SERVER ROOM 3. INSTALL MISSING PLATES |
|
01/23/2008 | ELECTRIC - FINAL | Not ready for Inspection | ROOF INSPECTION 1. NEED SERVICE RECEPTACLES FOR A/C EQUIPMENT TO BE WITHIN 25' 2. SAT DISHES TO BE GROUNDED 3. COAX CABLE ON ROOF TO BE INSTALLED IN NEAT AND WORKMANLIKE MANNER 4. COAX CABLE TO BE SUNLIGHT RESISTANT 5. NEED REVISED PLAN FOR SERVICE |