Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/01/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/18/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* BOB 512-799-4732 1. INSTALL MISSING KNOCK OUT IN JUNCTION BOX ABOVE BACK RESTROOMS. OK TO CLOSE CEILING. RECEIVED MONEY ORDER #08-768084595 FOR $150 FOR AFTER HRS. INSP. |
|
| 01/16/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE ALL TEMP WIRING & LIGHTING 2. MISSING SUPPORT CLIP ON 2X4 FIXTURE HARD LID 3. HAVE OPEN JUNCTION BOX 4. CEILING TILES NOT TO BE INSTALLED PRIOR TO INSPECTION 5. JUNCTION BOX FOR RTU NOT SIZED PROPERLY 6. NEED TIE WIRE FOR EXITS |